RO反渗透装置加药,我单位里是2级RO装置,请问一般常规设计下,加药一般加在哪一级哪一段?会有微生物超标风险吗 一级反渗透之前涉及到的加药系统有絮凝剂、阻垢剂、杀菌剂、还原剂等二级反渗透进水有加碱系统
帮忙翻译一下(中译英),不胜感激啊!!! Original water tank;Middle water tank;Clear water tank;Mechanical filter;Precision filter;The medicine washes the pump;Medicine tank washer;Level counter-seepage installment;Level counter-seepage installment;The medicine washes the filter;Tube pipe accessory;Measuring appliance;Central automatic control;Desalts the water tank;Desalts the water pump;Motorized valve;Pneumatic valve;Level high-pressure pump;Instead washes the pump;Canada gathers congeals the medicinal preparation installment;The medicine washes the part;The medicine washes the pump;Adds the antisludging agent installment;Imports the part;Stainless steel;Module;Central automatic control;Activated charcoal filter;Ultra filters the part;US.
怎样计算反渗透阻垢剂的加药量 加药量:每套反渗透系统的使用量。举例说明:产水量为75吨的纯水设备,那么RO装置的进水量约为100吨。反渗透阻垢剂月用量即为:100*3*24*30/1000=216KG(3为加药浓度ppm;24为每天工作时间小时;30为每月天数天;1000为换算单位g换KG)根据设备的使用量,确定周用量。按周用量确定加药箱大小,调整加药计量泵即可,使药剂平稳连续的注入RO设备即可。扩展资料:反渗透阻垢剂很大程度上延缓反渗透膜结垢,延长反渗透膜的使用寿命,这也就是反渗透膜为什么要加药的重要原因。反渗透阻垢剂的推荐浓度一般为3-8ppm,即反渗透设备每进水1吨需要添加3-8g的阻垢剂。月用量的计算公式:W=Q×S×H×30/1000,式中W为月用量(Kg);Q为反渗透设备的进水流量(m3/h);S为投加浓度(3-8ppm,即g/吨),H为反渗透设备的工作时间(小时);1000为g与Kg的换算量,若一台反渗透设备的产水量为75吨/小时,则进水需要至少100吨/小时,月用量为:100×3.5×24×30/1000=252KG2。反渗透阻垢剂一般添加在反渗透系统的保安过滤器,即精密过滤器之前,添加于加药装置中通过计量泵投加在反渗透设备的管道之中,反渗透阻垢剂可以直接使用原液也可稀释后再使用,稀释倍数不得超过10倍,即浓度不得低于10%。。