电动机点动控制与连续运转控制的关键控制环节是什么?其主电路又有何区别? 关键是有否自保持环节,有的为连续运转电路,没有的为点动控制电路。具体电路可以用点动按钮的常闭触点串接自保持接点,按点动按钮时同时断开自保持回路。
麻烦学机械英语的进来帮我翻译一下 点动控制Motor to move the control,连续运行控制continuous operation control,断纱自动停车控制parking control,automatic parking break yarn control,inverter speed control,wire,woven rings,yellow buttons A and B work the frequency,to move the operation,indicator light,circular woven machine,circular loom with soft,short the reset spring hook,C 电机点动控制closed,Deceleration,D prescription self-locking,E closed point of disconnect,self-locking,jog run,rotating spindle body,umbrella ring,double shuttle seat,on the operation panel,rack,dual-spindle bearing bushing seat,large helical gear,break yarn automatic stop device,a small helical gear,gear,braking,electrical,floor,the middle column,drafting system,zero parts,wire wheels,curved structure,before and after the middle rounds,caliber,weft tube,Adjustment screw,rotating spindle body,double rotating spindle body,wire wheels,sub-line wheel,worm shaft,turbine,divided by the yarn,clothing and weft,the inner wire wheel,change gear.
电动机的点动控制与连续控制的主电路有何区别? 主电路没有区别.控制电路不同.如要该电动机又可点动控制.又要连续控制则按下列方法接线:如要电机连续运转控制.就要在点动按钮两端并联1对接触器动合辅助触点.这种用接触器辅助触点使接触器线圈持续通电流的线路环节称自锁.(也称自锁线路、自锁作用、自锁功能、自锁环节等)如要电机点动控制运转控制.就要把点动按钮的常闭触点.串入上述自锁电路中即接触器动合辅助触点中.使接触器不能自锁.如经常点动启动电机.如吊车.因为电机启动电流是运行电流的4到7倍.,那么主电路上的接触器因频繁启动容易烧环触头.故接触器选用大一级的较好.连续控制的主电路的接触器不用加大。
3个按钮,1个接触器控制,即点动又可以连续转动,? 要按钮联锁才能实现 追问:当然知道要联锁,怎么联,回答:把点动的那个按钮常闭串在 接触器 辅助触点(自锁)线路中即可
既可点动控制又可连续运转控制的电路图 电路图如下:其中2113SB2为连续工作启动按钮5261。SB3是复合按钮,用于点动工作。4102当按下SB3时,接触器1653线圈有电,主触点闭合,电动机启动。串联在自锁触点支路的常闭按钮断开,使自锁失效。松开SB3时,接触器线圈立即断电,电动机停车。可见SB3只能使电动机点动工作。扩展资料:电动机的保护短路保护:当控制电路发生短路故障时,控制电路能迅速断开电源,熔断器FU1作为主电路的短路保护。熔断器FU2作为控制电路的短路保护。过载保护:热继电器FR作为电动机的过载保护。当电动机过载、堵转或断相等都会引起定子绕组的电流过大,热继电器会根据电流的热效应,使热继电器FR动作。即FR的常闭触点断开,使KM线圈断电,从而使KM主触点断开,切断电动机的电源。欠压和失压保护:依靠按钮的复位功能和接触器本身的电磁机构来完成。当电动机正在运行时,如果电源电压因某种原因过分地降低或消失时,接触器KM衔铁释放,电动机停止,同时KM自锁触点断开。接触器KM线圈也不可能自行通电,即电动机不会自行启动,要使电动机启动,操作者必须再次按下启动按钮。